The LOGIKMODULE is equipped with two dual-color LEDs:
-
Power/Boot LED – upper LED
-
Status LED – lower LED
Each dual-color LED consists of a green and a red LED. By combining both colors, an orange indication can also be displayed.
Power/Boot LED
|
LED Indication |
Meaning |
|---|---|
|
Off |
The device is not operational. No operating voltage is applied. |
|
Green |
The device is operational. |
|
Flashing orange |
The device is in the boot phase. |
Status LED
|
LED Indication |
Meaning |
|---|---|
|
Off |
The device is in the boot phase. |
|
Flashing green |
The device has started. The LED flashes regularly as a “heartbeat” indication. The flashing frequency increases depending on the device load. |
|
Flashing red |
On the KNX/TP version, communication via KNX is taking place. |
Behavior During Device Startup
As soon as the LOGIKMODULE is supplied with power, the Power/Boot LED lights up green.
Approximately 2 to 3 seconds after switching on, the red component of the LED also begins to flash. As a result, the Power/Boot LED appears flashing orange, indicating that the boot process is in progress.
Once the boot process has been completed, the Power/Boot LED remains permanently green. At the same time, the Status LED begins flashing green, indicating normal device operation.
The flashing frequency of the Status LED varies depending on the device load.
Note
The complete startup process of the LOGIKMODULE takes approximately 3 minutes.
///