Installation and Electrical Connection

Secure Operation

To operate the device with KNX Data Secure, proceed as follows:

  • Enable Secure Commissioning in the ETS.

  • Remove the Device Certificate from the device and store it in a safe place.

  • Enter or scan the Device Certificate and add it to the ETS project.

  • Recommendation: Use a high-resolution camera to scan the QR code.

  • Document all passwords and keep them in a secure location.

Installing and Connecting the Device

  • Observe the specified cable routing and minimum cable clearances.

  • Mount the device on a DIN rail.

  • Connect the bus cables to the KNX bus terminals (see Figure 1), observing the correct polarity.

  • Connect the superordinate line to the lower bus terminal (10). The device is powered via this connection.

  • Connect the subordinate line to the upper bus terminal (1).

  • Fit the protective caps to the KNX bus terminals to protect against hazardous voltages.

Note

The subordinate line requires a separate KNX power supply.


///