Thermostat

Temperature Unit

Select the temperature unit used by your KNX thermostat.

  • Celsius

  • Fahrenheit

Query Current Heating/Cooling Mode (EIS 14)

Enter the group address from which the current heating/cooling mode is reported.

Default values:

  • 1 = Off

  • 2 = Heating

  • 3 = Cooling

Change Target Heating/Cooling Mode (EIS 14)

Enter the group address used to change the target heating/cooling mode.

Default values:

  • 1 = Off

  • 2 = Heating

  • 3 = Cooling

  • 4 = Automatic

Query Target Heating/Cooling Mode (EIS 14)

Enter the group address from which the target heating/cooling mode is reported.

Default values:

  • 1 = Off

  • 2 = Heating

  • 3 = Cooling

  • 4 = Automatic

Off Mode Value (0–255)

Value sent for the Off operating mode.

Heating Mode Value (0–255)

Value sent for the Heating operating mode.

Cooling Mode Value (0–255)

Value sent for the Cooling operating mode.

Automatic Mode Value (0–255)

Value sent for the Automatic operating mode.

Current Temperature State (EIS 5 / 0.0–100.0)

Enter the group address from which the current temperature is reported.

Supported values:

  • 0.0 °C to 100.0 °C

  • 32.0 °F to 212.0 °F

Change Target Temperature (EIS 5 / 0.0–100.0)

Enter the group address used to change the target temperature.

Supported values:

  • 10.0 °C to 38.0 °C

  • 50.0 °F to 100.4 °F

Query Target Temperature (EIS 5 / 0.0–100.0)

Enter the group address from which the target temperature is reported.

Supported values:

  • 10.0 °C to 38.0 °C

  • 50.0 °F to 100.4 °F

Change Heating Threshold (EIS 5 / 0.0–100.0)

Enter the group address used to change the heating threshold.

This value is only effective in Automatic mode.

Supported values:

  • 0.0 °C to 25.0 °C

  • 32.0 °F to 77.0 °F

Query Heating Threshold (EIS 5 / 0.0–100.0)

Enter the group address from which the heating threshold is reported.

This value is only effective in Automatic mode.

Supported values:

  • 0.0 °C to 25.0 °C

  • 32.0 °F to 77.0 °F

Change Cooling Threshold (EIS 5 / 0.0–100.0)

Enter the group address used to change the cooling threshold.

This value is only effective in Automatic mode.

Supported values:

  • 10.0 °C to 35.0 °C

  • 50.0 °F to 95.0 °F

Query Cooling Threshold (EIS 5 / 0.0–100.0)

Enter the group address from which the cooling threshold is reported.

This value is only effective in Automatic mode.

Supported values:

  • 10.0 °C to 35.0 °C

  • 50.0 °F to 95.0 °F

Current Humidity State (EIS 5 / 0.0–100.0)

Enter the group address from which the current humidity is reported.

Supported values:

  • 0.0 to 100.0 %

Change Target Humidity

Enter the group address used to change the target humidity.

Query Target Humidity

Enter the group address from which the target humidity is reported.


///