The DUODMX GATEWAY KNX SR REG is designed for installation in electrical distribution boards and is housed in a DIN rail enclosure (4 TE / 4 module units) for mounting on a DIN EN 60715 rail.
The device features two independent DMX interfaces, each of which can be configured separately to operate as either a DMX Master (transmitting) or a DMX Slave (receiving).
Specifications
Power Supply
-
Terminal connection: 12–32 V DC
-
Power consumption: ≤ 1.2 W
Mechanical Data
Mounting
-
DIN rail enclosure: 4 TE (4 module units)
-
DIN rail according to EN 50022 – 35 × 7.5 mm
Dimensions
|
Variant |
Dimensions (W × H × D) |
|---|---|
|
REG version |
70 × 90 × 63 mm |
Interfaces
-
KNX via terminal connection (Twisted Pair)
-
Network via RJ45 connector
-
2 × DMX512 via terminal connection
-
Wire cross-section: up to 1.5 mm²
-
-
Push-button input via terminal connection
-
Wire cross-section: up to 1.5 mm²
-
Variant
Device Variant: KNX SR REG (Article No. 12521)
The KNX SR REG variant supports both the transmission of DMX commands based on incoming KNX TP telegramsand the transmission of KNX TP telegrams based on incoming DMX commands.
A network connection is not required for normal operation.
The Master/Slave function (Transmit/Receive) can be configured independently for each DMX interface.
KNX telegrams are transmitted and received via the KNX Twisted Pair bus. In addition, KNX telegrams can also be received over the network using KNXnet/IP Routing.
///