Secure Operation
Before commissioning the device with KNX Data Secure, complete the following steps:
-
Enable Secure Commissioning in the ETS.
-
Remove the Device Certificate from the device and store it in a safe place.
-
Enter or scan the Device Certificate and add it to the ETS project.
-
Recommendation: Use a high-resolution camera to scan the QR code.
-
Document all passwords and keep them in a secure location.
Installing and Connecting the Device
-
Observe the specified cable routing and the required cable clearances.
-
Mount the device on a DIN rail.
-
Connect the bus cables to the KNX bus terminals (see Figure 1), observing the correct polarity.
-
Connect the superordinate line to the lower bus terminal (10). The device is powered via this connection.
-
Connect the subordinate line to the upper bus terminal (1).
-
Fit the protective caps to the KNX bus terminals to protect against hazardous voltages.
Info
The subordinate line requires a separate KNX power supply.
///